What is the maximum conductor length allowable on a TVSS EBA and EMA Surge Suppressors?

Issue:
Are there any wire length restrictions when installing the TVSS EMA and EBA Surge suppressors?

Product Line:
Surge suppressors

Environment:
TVSS EBA, TVSS EMA

Cause:
Installation

Resolution:
The conductors for the TVSS EBA and TVSS EMA units should be 24-36 inches long, or less. Longer conductor lengths diminish the effectiveness of the surge suppression capabilities of the unit.

 