What is the SCCR (Short Circuit Current Rating) for a HU368, HU368AWK or HU368R non-fusible safety switch?


Product Line:
HD Safety Switch

Application regarding SCCR

These switches are suitable for use on a circuit capable of delivering not more than 200,000 rms symmetrical amperes, 600Vac maximum, when protected upstream by Class L or Class T fuses rated 1200 ampere maximum. If not protected by a Class L or Class T fuse, the withstand rating is 10KAIC.