Do circuit breakers have to be de-rated due to high altitudes?

Yes, per Data Bulletin  0100DB010106/01
Altitude          Amps Multiplier              Voltage multiplier
0-6600 ft                           1                                              1
6600-8500 Ft                 .99                                           .95
> 8500 Ft                         .96                                            .80

(Revision to FAQ 2003254 Question answered and Bulletin number referenced)