Technical FAQs

Ask a Question

What is the difference between the GV2L and GV2ME?

Product Line:
 
GV Manual Motor Starters and Protectors
 
Resolution:

The GV2L devices are similar to the GV2M manual starters but provide magnetic protection only. The GV2M devices provide thermal overload protection as well. Neither device is UL489 listed for use as a circuit breaker in the United States.

 
Was this helpful?
What can we do to improve the information ?