Technical FAQs

Ask a Question

What is the lug torque specification for a Powerpact J frame circuit breaker?

Product Line:
Circuit Breakers
PowerPact J

Electrical Distribution Equipment

The standard al/cu lugs are rated at 225lb-in and require a 5/16 in hex bit torque wrench. See below for lug information.
The AL175JD ( 150 - 175A) is 225lb - in.
The AL250JD ( 200 - 250A) is 225lb - in.
The CU250JD (150 - 250A) is 250lb - in

See instruction bulletin, 48940-221-02

CTA-ID : 2046449
Was this helpful?
What can we do to improve the information ?