Four-pole NS250N breaker: What is the difference bewteen a 4P3T and a 4P4T?

Four-pole or 4P breaker - the ``3T`` indicates the 4th pole is switched, but has no overcurrent protection, while the ``4T`` indicates there is a protection element in each of the four poles.