What type of wire binding screw is used with AL150HD lugs and what size it? What is the size , or type of tool that is used to torque them ?

An Allen wire binding screw is used and a 3/16`` Allen wrench is needed to torque screws to 50 in lbs for #14-#10 awg wire and 120 in. lbs for #8-3/0 Al/Cu conductors

CTA-ID : 2045502