Can a Model 5 MCC Bucket be placed in new Model 6 MCC section

Issue:
Can  a Model 5 MCC Bucket be placed in new Model 6 MCC section

Product Line:
Motor Control Centers

Environment:
Maintenance / Installation

Cause:
Clarification

Resolution:
The model 5 bucket  will mount into a new Rev 05 ( Oct 2005 and Later) Mdl 6 MCC structure. You  will have to use the shelf that comes in the new section and drill out the pin that is there for the butterfly to latch the Bucket in. Note the old Model 5 shelf, or Pre Oct 2005  Mdl 6 MCC shelf,  will not work