Will a K frame breaker such as a KA, KH, KC or KI fit into an HCN panel?

Issue:
Can you install a KA, KH, KC or KI breaker into an HCN I-line panel?

Product Line:
Distribution Panelboards

Environment:
I-Line HCN panelboard

Cause:
Fit

Resolution:
No, a K frame breaker will not fit into an HCN panel.  If the panel is wired to 480V, the largest branch available is a 150A H frame.  If wired to 240V the largest is a Q frame breaker up to 225A.  