Can the M800S, M800R, P1200S and P1200R circuit breaker enclosures be wired for any combination of top or bottom feed and load consisting of the following:<br />-top-feed, top-load<br />-top-feed, bottom-load<br />-bottom-feed, top-load<br />-bottom-feed, bottom-load

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Cause:
Application

Resolution:
The answer to this question depends upon whether or not a neutral is installed. When a breaker is installed into one of these enclosures, on each side of the breaker there is a gutter. These gutters may be used either for installing a neutral, or as wiring gutter.
-If NO NEUTRAL is installed, either or both gutters may be used for wiring, and the enclosure is approved for any combination of top/bottom feed and load.
-If a 100% NEUTRAL is installed, since one of the gutters is now in use, the other gutter is of sufficient size to accommodate all the line and load cables, and the enclosure is approved for any combination of top/bottom feed and load.
-If a 200% NEUTRAL is installed (M800S and M800R only), since both gutters are now in use, they may not be used as wiring gutter. Wires must enter and exit the enclosure from the endwall directly facing the lugs, which means the enclosure is restricted for top-feed/bottom load, or bottom-feed/top load.