What are the repair parts for a CUM400CB, Series M01, Combination Service Entrance Device?

Issue:
Repair parts

Product Line:
Combination Service Entrance Device

Environment:
400A CSED

Cause:
Replacement parts required

Resolution:
NOTE: WIRING DIAGRAM AND LABELS ARE NOT INCLUDED ON THE PARTS LISTED BELOW.
Only the parts listed below are considered field replaceable.
Meter Cover - 4056250650 Also requires insulator and rivets noted below.
Meter Cover Insulator - 4056138202 and Rivets (2) 2430313190
Meter Cover Mounting Screw - 4020513001K (10 screws in kit, only one used to mount cover)
Main Breaker Section Cover - 4056258950
Main Breaker Section Cover Mounting Screws - (3) 2142217101
Utility Pullbox Cover - 4056232801 (Handles not included, see below)
Utility Pullbox Cover Handles - (2) 2940101103 and Rivets (8) 2430315290
Utility Pullbox Cover Mounting Screws - (2) 4020513001K and (3) Sealing Screws X1299
Interior Deadfront Trim - 7329420650
Interior Deadfront Trim Mounting Screws - 4020513001K (10 screws in kit, only 6 used to mount trim)
Interior Deadfront Trim Handle - (1) 2940101103 and Rivets (4) 2430315290
Meter Base Assembly - 7329490250
Mounting Channel - 4056142003
Factory Installed Main Breaker - DGP36400E20LH (Obsolete and no longer available. Can be replaced with LJL36400U31X. Mounting Kit S36967 is also required. The lugs on the ON end of the breaker must be removed for connection to the busbars. The B phase (center) lug should also be removed from the OFF end of the breaker.)
Utility Lug Mounting Hardware - 4056211850
NOTE: WIRING DIAGRAM AND LABELS ARE NOT INCLUDED ON THE PARTS LISTED ABOVE.