In an NF panel with a 100 amp ED, EG or EJ branch breaker what is the largests amperage breaker you can mount across from the 100 amp?

Issue:
In an NF panel with a 100 amp ED, EG or EJ branch breaker what is the largests  amperage breaker you can mount across from the 100 amp?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
70 amps maximum.