Technical FAQs

Ask a Question

What are the clearance requirements for SquareD/Schneider Electric Transformers from walls or other obstructions?

Clearances vary with type of Transformer installed

Product Line:
LV Transformers

Applies to Low Voltage Transformers by SquareD/Schneider Electric

Transformers produce heat in operation, so must have clearance to obstructions


Older, non-EE Ventilated dry type Transformers must be installed so that a minimum of 6 inches clearance is available between a ventilation opening and any wall or other obstructions. Energy Efficient Transformer require a minimum of 3`` clearance from ventilated openings. This does not apply to bottom ventilation openings. Non-ventilated Transformers should be a minimum of 3 inches from any obstruction on all sides and top. Epoxy resin filled Transformers may be mounted directly on the wall, but require 12 inches on both sides, top and bottom. Unit substation style Transformers require a minimum of 12 inches around the ventilation openings, and local codes may exceed that. The clearance requirement is clearly marked on the nameplate of the Transformers.

CTA-ID : 2044982

Was this helpful?
What can we do to improve the information ?