Technical FAQs

Ask a Question

When ordering a factory assembled 400 amp main lug only NF panelboard with subfeed lugs, does changing the main lugs to accommodate 750MCM conductors also change the sizing of the subfeed lugs to 750 MCM?

Issue:
When ordering a factory assembled 400 amp main lug only NF panelboard with subfeed lugs, does changing the main lugs to accommodate 750MCM conductors also change the sizing of the subfeed lugs to 750 MCM?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Yes. Both main lug and subfeed lug sizes change to 750MCM.


CTA-ID : 2044792
Was this helpful?
What can we do to improve the information ?