When ordering a factory assembled 400 amp main lug only NF panelboard with subfeed lugs, does changing the main lugs to accommodate 750MCM conductors also change the sizing of the subfeed lugs to 750 MCM?

Yes. Both main lug and subfeed lug sizes change to 750MCM.