What is the required distance between hangers or how many hangers are required for I-Line II busway?

Issue:
How many feet apart do you mount hangers for I-Line II busway?

Product Line:
Busway

Environment:
I-line II

Cause:
installation and mounting

Resolution:
Indoor horizontal busway requires one hangar at least every 10 feet. Vertical Indoor busway requires one hanger at least every 16 feet. Outdoor Feeder Busway requires one hanger at least every 5 feet in both the vertical or horizontal orientations.


 