What is the torque value needed for the 1/2``-13 VISI-TITE Nut used in EZM for connection the horizontal cross busses together after the outer head has been broken off?

It is 50 lb.-ft. of torque is required for the inner hex head nut once the VISI-TITE nut head has been removed . This information is also provided on the wiring diagram.