In configuring an NF panelboard on Product Selectors/EQM, does installation of an isolated ground also include the regular ground? Customer wants a 6 wire panel configuration. What is this?

Issue:
In configuring an NF panelboard on Product Selectors/EQM, does installation of an isolated ground also include the regular ground?    Customer wants a 6 wire panel configuration.   What is this?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
Both standard ground and isolated ground must be selected separately on the Product Selectors program. A six wire configuration includes (3) phase conductors (1) neutral (1)isolated ground and (1) regular ground.


CTA-ID : 2039777