What is the operational voltage and current of the shunt trip, catalog number S29386, used on circuit breaker HGA36070SA?

Product Line:
Circuit Breakers
PowerPact H

Electrical Distribution Equipment

The operational voltage of that shunt trip is: 110-130V AC. The S29386 operates at <10VA, so the current is approximately .083A.

CTA-ID : 2040757