What is the lug wire range for an 800 amp main lugs I-Line panel?<br />

The lugs on this panel will accept 4-#3/0 to 750kcmil Al/Cu per phase and neutral. However, conductors should be limited to 3-#3/0 to 500kcmil Al/Cu per phase and neutral to conform to UL/CSA wire bending space.``)