What is the terminal lug data(or wire range) for the MP86200 and are there alternate lugs available?

Issue:
Product terminal lug data

Product Line:
Meter Pak Metering Equipment

Environment:
Main lug wire size

Cause:
Application

Resolution:
The standard terminal lug data(or wire range) for the MP86200 is as follows:
The device will accept as standard (2) 3/0 AWG to 500 kcmil Al/Cu wires per phase and neutral.

Alternate(or optional) Lugs for the device are:
1) The Lug kit catalog number MMLK250 will accommodate (1) 1/0 AWG to 600 kcmil, or (2) 1/0 AWG to 250 kcmil AL/CU wire(s) per phase and neutral.
2) The Lug kit catalog number MMLK600 will accommodate (2) #2 AWG to 600 kcmil AL/CU wires per phase and neutral.
3) The EUSERC Lug Landing kit catalog number MMSK2 will accommodate (1) 2-Hole Tang Lug per phase and neutral. The Wire bending with MMSK2 Lug Landings installed is still limited to (2) 600 kcmil AL/CU Lugs per phase and neutral.

THERE ARE NO OTHER LUG KITS OR WIRE SIZES THAT THIS DEVICE WILL ACCEPT