Where can an EZM600FTLK3 feed-thru lug kit be used, and what wire ranges will it accommodate?

Issue:
Application

Product Line:
EZM

Environment:
Application

Cause:
Correct application of feed thru lug kit

Resolution:
The EZM600FTLK3 feed-thru lug kit is suitable for use only in 800A EZM-TB Tap Boxes (Catalog Numbers: EZM1800TB, EZM3800TB, EZM1800TBCU, and EZM3800TBCU). Some documents have erroneously stated that the kit was suitable for use only with 800A EZM-TBCU Tap Boxes.  
Kit includes (4) Lugs per phase and neutral and all mounting hardware.
Lug wire range for (1) 1/0 AWG - 750 kcmil AM/CU, or (2) 1/0 AWG - 300 kcmil AL/CU.