Can an empty bucket be ordered for a model 6 MCC?

Issue:
Can an empty bucket be ordered for a Model 6 MCC?

Product Line:
Mdl 6 MCC

Environment:
Ordering

Cause:
Availbility

Resolution:
Yes, but it must be done through the MCC Product Selectors . The bucket itself is 9.75"D , which is far short of the vertical bussing farther back in the section. There is no provision for getting power from the Vertical , or Horizontal bussing. Power to compartment would need to be thru the vertical wireway troughs and opening in Empty mtg bucket. The Buckets come in 3" high increments starting at 6"- 48" H