What is the terminal range for a 800 amp Main Lug I Line interior?

Issue:
What is the terminal range for a 800 amp Main Lug I Line interior?

Product Line:
I line panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
4-#3/0 to 750kcmil Al/Cu per phase and neutral, however, there is only wire bending space available for 3-#3/0-500kcmil AL/CU.


CTA-ID : 2036387