Do we have a busway offering with a 200% rated neutral?


Issue:
Do we have a busway offering with a 200% rated neutral?

Product Line:
Busway

Environment:
I-line II busway

Cause:
Product features/requirements

Resolution:
No. The amperage of the busway will need to be double the anticipate load. ( i.e. for a 600A load, a 1200A busway will need to be ordered )

 