Can a two pole 20A GFCI can be ordered with an auxiliary or an alarm contact? Can they be field installed? Will it require an extra space?

A QO type GFI breaker can be ordered with an auxiliary contact type 1A or with 1B, or an alarm switch. It is not field installable. It will require an extra space in the panel. The QO type GFI breaker can not be ordered with shunt trip or undervoltage release accessories.