Technical FAQs

Ask a Question

What is the maximum amperage breaker available that can be installed into the largest size I-Line panel?

Issue:
Largest amp size breaker

Product Line:
Panelboards

Environment:
I-Line

Cause:
Maximum rating

Resolution:
The highest bus rating for I-line panels is 1200A. Because of this, the largest breaker available to plug on to the I-Line bus is also 1200A. However, a breaker this large can only be used on the HCR-U type panelboards.


CTA-ID : 2035478
Was this helpful?
What can we do to improve the information ?