Does a Surge Supression device such as a TVS2EBA24A require a circuit breaker or other means of disconnect? If so, what amperage?

Issue:
Does a Surge Supression device such as a TVS2EBA24A require a circuit breaker or other means of disconnect?  If so, what amperage?

Product Line:
Surge Protection.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
To protect a TVS2EBA24A, you may use a 3 pole, 30A (minimum) breaker, although a 60A breaker is preferred.