What is the catalog number for an optional main lug kit that will accept 2-500 kcmil per phase for a 400 amp main lug NF Panel?

Issue:
Main lugs option

Product Line:
Panelboards

Environment:
NF

Cause:
Larger 500kcmil cables

Resolution:
The NALV4 compression lug kit is an optional main lug kit which will accept 2-500 kcmil wires per phase for a 400 amp main lug NF Panel but only for the pre-series E1 panel