On a U-line starter, how does the auto reset work?

In Auto Reset mode, the U-line starter (with an Advanced Control Unit and the LUFDA10 function module) operating handle remains in the ``ready`` position but the coil is de-energized and the power poles open on an overload. After a motor cool-down, the unit resets and the power poles close. Proper wiring is essential

On a short circuit fault, the handle moves and the device will have to be manually reset.