Technical FAQs

Ask a Question

Will a 9013G switch handle 20A at 230V 1phase and 3HP?

Issue:     
Will a 9013G switch handle 20A at 230V 1phase and 3HP?

Product Line:
Pressure Switches

Environment:
9013 Pressure Switches

Cause:
Will a 9013G switch handle 20A at 230V 1phase and 3HP? 

Resolution:
The 9013G are not current rated devices. They are HP rated devices only. To use on 3 phase circuits, wire 2 phases through the 2 poles of the switch and direct wire the third phase to one of the motor leads. This makes the lead live when the pressure switch is OFF.

 
Was this helpful?
What can we do to improve the information ?