Can you install a SDSA1175, SDSA3650, QO21175SB or HOM2175SB TVSS unit in a Mini Power Zone MPZ type Transformer?

Transient Voltage Surge Suppression products in Mini Power Zone Transformers (MPZ)

Product Line:
LV Transformers

Applies to Mini Power Zone (MPZ) Transformer products from SquareD/Schneider Electric

The application of a Mini Power Zone (MPZ) Transformer and specification of TVSS Transient Voltage Surge Suppression


No. The Mini Powerzone is not UL listed for the installation of any surge/TVSS unit inside the enclosure or in the loadcenter section.   However, TVSS Transient Voltage Surge Suppression may be connected external to the MPZ enclosure