What alternate lugs are available for the EZM1800TB?

ISSUE:
Alternate Lugs

PRODUCT LINE:
EZM Metering

ENVIRONMENT:
Alternate Lugs


CAUSE:
Change in Wire Size

RESOLUTION:
Yes, alternate lugs are available for this device.

Standard Lugs porvided for this EZM1800TB includes capacity for (4) 3/0 AWG - 500 kcmil AL/CU

For lugs to accept (2) #1/0 AWG - 600 kcmil AL/CU or (4) #1/0 AWG - 250 kcmil AL/CU wires per Phase and Neutral:
Order (2) MMLK250 lug kits. Each kit consists of three 2 barrel lugs capable of terminating (1) 600 kcmil or (2) 250 kcmil maximum conductors.
Two of these 2 barrel lugs will be installed per phase and neutral for a total of six 2 barrel lugs required per device.

For lugs to accept (2) #1/0 AWG - 750 kcmil AL/CU or (4) #1/0 AWG - 300 kcmil AL/CU wires per Phase and Neutral:
Order Lug Kit part number: 7329696650 This kit includes ``L-Shaped`` connectors with (2) AL2500PA lugs mounted per Phase and Neutral.
A new cross bus barrier is also provided in this kit along with all required mounting hardware.

For Lug Landing Pads to accommodate (2) compression type lugs per Phase and Neutral
Order Lug Kit part number: 7329687650 This kit includes ``L-Shaped`` connectors with studs and keps nuts
to mount (2) lugs per Phase and Neutral, supplied with NEMA Standard spacing of 1-3/4`` between lug mounting holes,
a 2`` horizontal spacing between lugs. Order lugs separately.