What is the wire range for the compression lugs supplied in the H12LKE2 lug kit for the Heavy Duty Safety Switches?

Issue:
Product design features

Product Line:
Heavy Duty Safety Switches

Environment:
Compression Lugs

Cause:
Application:

Resolution:

Each compression lug will accept (1) 500 - 750 kcmil aluminum or (1) 500 kcmil copper conductor. Four lugs are supplied per connector assembly and two connector assemblies are supplied per H12LKE2 kit. One kit will supply four compression lugs for the line and load side of one switching pole or neutral of the 1200A switch. The compression lug supplied is an Anderson(or Hubbell) VCEL07512H1.


 