Technical FAQs

Ask a Question

Is there a B phase modification kit for NF B phase hi-leg panels to enable putting a three pole breaker in the panel?

Issue:
Is there a B phase modification kit for NF B phase hi-leg panels to enable putting a three pole breaker in the panel?

Product Line:
Panelboards.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
NF B phase high leg panels must be ordered as factory assembled. Three pole spaces should be called for if three pole breakers are to be added in the future. B phase high leg panels ordered with all single pole spaces cannot be modified in the field.






CTA-ID : 2033620
Was this helpful?
What can we do to improve the information ?