Can you defeat GF and thermal imaging at the same time with the FFTK?

Issue:
Can you defeat GF and thermal imaging at the same time with the FFTK?

Product Line:
Test Equipment

Environment:
Full Function Test Kit (FFTK)  S33595
FFTK instructions 48049-183-06, the ground fault inhibit section.

Cause:
Want to defeat both.

Resolution:
Yes,  activating ground-fault inhibit will automatically activate thermal-imaging inhibit and enable zone selective interlocking (ZSI) self-restraint.