Does the ATV61 or ATV71 have the COS (cosine, power factor) parameter?

No. There is no power factor setting in these drives. It is not needed in these drives.
Set the other motor parameters in menu 1.4 (Motor Control - drc)
Run auto tuning with the motor cool.