Technical FAQs

Ask a Question

Customer has connected a SDSA3650 surge supressor on an open delta power source and the monitor lights won`t come on.

The SDSA3650 requires a neutral connection for proper operation. Wiring to an open delta power source does not supply a neutral connection, so is a misapplication of the product.

CTA-ID : 2032836
Was this helpful?
What can we do to improve the information ?