Does the EZM main device used in a EZM Line-up, Disconnect all the power to the EZM meter branch devices connected in that line-up?

Issue:
Product Design Features

Product Line:
EZM Metering

Environment:
EZM Main Devices

Cause:
Product operation

Resolution:
Yes. The EZM Main Device(either a Fusible Switch or Main Circuit Breaker), does control the power to all of the EZM meter branch devices in the same line-up(or that are connected to that EZM Main Device).

NOTE: The EZM Main Terminal Boxes do NOT control the power to the EZM meter branch devices, because there is NO overcurrent device or disconnect within the EZM main terminal box. When a EZM Main Terminal Box application is used as the EZM Main, the tenant circuit breakers (no more than six are allowed in one line-up) in the branch units are considered the Service Disconnects.