Issue:
Application


Product Line:
LVDO

Environment:

Cause:
It is typically acceptable to substitute a circuit breaker with higher interrupting ratings for one with lower interrupting ratings, if they are otherwise alike in other characteristics. 

Resolution: 

NOTE:  DS and DSL circuit breakers are obsolete.  No, a DSL206 cannot replace a DS206 circuit breaker because the DSL206 is eight inches deeper than the DS206 due to the limiters located at the back of the device. 