Why am I not getting any output voltage on an XUK0ARCTL2 photo electric sensor?<br /><br />

The output relay of this sensor is dry. No output will be produced until voltage is applied to the relay common. There is an error in the wiring diagram on pg. 53 in the Solid State Sensors catalog Doc. # 9006CT0101. Correct colors are BRN = L1 or DC positive, BLU = L2 (neutral) or DC common, GRY = relay common, BLK = N.O. contact, WHT = N.C. contact.