Why isn`t AL100FD field installable on EDB, EGB, and EJB 15-30 amp breakers anymore?

Issue:
Why isn`t  AL100FD field installable on EDB, EGB, and EJB 15-30 amp breakers anymore?

Product Lines:
E Frame, NF Panelboards

Environment:
Wiring in NF Panelboards

Cause:
Need a larger wire sizes for E Frame breaker 30 A and below.

Resolution:
AL100FD is no longer a field installed option on the latest 15-30 amp breakers due to a molding process change and associated rejections features.
AL100FD can be factory installed using suffix LH, like EDB34020LH.
CU100FD is still a field installable option for 15-30 amp breakers.

CTA-ID : 2031634