What is the temperature rating of the main lugs used in ALL the MP METER-PAK devices?

Current product design features

Product Line:
MP meter pak metering

Lug temperature rating

Wire type for application


Main lugs used in ALL the MP METER-PAK metering equipment are temperature rated 75 degree C maximum. For use with Wire (AL/CU) having 90 degree C insulation in this equipment, the wire MUST be sized per the 75 degree C maximum listing in NEC Table 310-13.  For information on temperature ratings refer to NEC Section 110.14(1)(b)(2).