What fusing is allowed in the HVLCCA14305D HVL/cc Digest Listed Switch? Does the HVLCC20305D use parallel fusing?

The HVLCCA14305D Switch is 14.75`` wide and will accept single barrell fuses only. At 5kV up to 450E. The HVLCC20305D is 20.00`` wide and will accept double barrell fuses. At 5kV up to 600E.