What is the rating plug for a 1200 amp PJ Micrologic trip unit breaker to change amperage to 800 amps?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
S48820 rating plug type C. For Micrologic trip unit applications only. This rating plug has a .667 setting to achieve 800 amps.
 