Do Powerpact H and J Thermal Magnetic Breakers have adjustment dials?

Issue:
Do Powerpact H and J  Breakers  have a magnetic adjustment dial?

Product Line:
Powerpact H and J

Environment:
Thermal magnetic

Resolution:
H frame:  No the thermal and magnetic settings are fixed.
J frame:  Yes. The thermal setting is fixed, however the magnetic settings is adjustable by a dial that is adjustable from 5 to 10 times the handle amp rating.