What is the joules rating for the SDSB1175 surge breaker?

Square D does not measure our TVSS/Surge Arrestors in joules, but in surge current rating per kA). Joule ratings can be manipulated by using a different testing wave form other than 8 x 20 Cris Buck TVSS Tag