Customer needs a temperature switch for a 180 degree F application.

9025 temperature switches are now obsolete with no direct replacement. However, if answering the question, choose a switch where the operating temperature is close the center of the range of the device. In this case, the 9025GXW3 and 9025GXW4 would both technically fall within the parameter listed, but the 9025GXW3 would be the better choice because 180 degrees is closer to its operating midpoint. In choosing the 9025GYW, the 9025GYW3 would be the only alternative.