Is there a NEMA 3R outdoor enclosure available for the Class 8910 Type SYD, DPA122, DPA123 definite purpose contactors?

Issue:
Is there a NEMA 3R outdoor enclosure available for the Class 8910 Type SYD, DPA122, DPA123 definite purpose contactors?

Product Line:
Definite Purpose Contactors

Environment:
Products sold and used in the United States

Cause:
Outdoor application

Resolution:
The 9991SEH1 enclosure which is designed for the Class 8536 Types SEO NEMA size 3 contactor is suitable for use with the 8910DPA122, 8910DPA123 and 8910SYD138 contactor. The 9991SFH1 enclosure which is designed for the Class 8536 Types SFO NEMA size 4 contactor is suitable for use with the 8910SYD230 contactor. There is no option for the 8910SYD368, suggest the use of a commerical enclosure.

Note: The use of this enclosure will also require replacement of reset assembly with 9001K51 closing plate.


CTA-ID : 2031304