Technical FAQs

Ask a Question

Can the EDB, EGB, EJB type breakers be used on 400 Hz systems?

Yes. The thermal de-rating for all amperages is 0.97. The magnetic rerating multiplier is 2.6. The interrupting rating is 10% of the 60 Hz interupting rating.


CTA-ID : 2030256
Was this helpful?
What can we do to improve the information ?