Where are the SB thermal unit selection tables in the Digest?

The SB slow trip thermal units are selected per the Digest instructions preceding the tables. Selection is the same as for the Type B thermal units except using 93% of the full load current value (102% for class 8198 devices) for motors with a service factor of 1.15 to 1.25 . The S prefix is then added to create the SB catalog number.